The EZCT-2000C is Vanguard’s third-generation microprocessor-based current transformer test set. Designed specifically for CT testing, the EZCT-2000C has the following outstanding features that can greatly increase productivity and save time during the commissioning stage.
The EZCT-2000C’s test leads can be connected to all the CT output terminals, and the complete CT test can be performed automatically without any operator intervention.
Key Features |
Performs CT excitation, current-ratio, polarity, and phase angle tests |
Measures insulation resistance and winding resistance of the CT seconday windings |
Measures the CT’s secondary burden |
Test record header information including company, substation name, circuit ID, manufacturer, CT serial number, operator name, and test record-comments |
Built-in 4.5-inch wide thermal printer |
Plot Multiple Saturation Curves |
Stores up to 128 CT test plans and 140 test records internally |
USB, Bluetooth, and USB Flash drive interface |
Specifications | |
EZCT-2000C Current Transformer Test Set | |
Features | Parameters |
Type | Portable current-transformer test set |
Dimensions | 19″W x 13″H x 16″D (48.3 cm x 33cm x 40.1 cm) |
Weight | 73 lbs (33.1 kg) |
Input Power | 100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz |
Measurement Method | IEC 60044-1 IEC 61869 ANSI/IEEE C57.13.1 ANSI/IEEE C57.12.90 |
Test Output Voltages | 0 – 50 Vac @ 10A max 0 – 300 Vac @ 10A max 0 – 500 Vac @ 5A max 0 – 1200 Vac @ 1.2A max 0 – 2000 Vac @ 1A max |
Current Source | 1 – 20A @ 0 – 15 Vac |
Current Source Display | Test current and current on-time |
Voltage Reading Range | 0 – 2,200 Vac Accuracy: ±1.0% of reading, ±1 V |
Current Reading Range | 0 – 10A Accuracy: ±1.0% of reading, ±0.02A |
CT Current Ratio Range | 0.8 – 999: ±0.1% 1000 – 1999: ±0.3% 2,000 – 4,999: ±1% 5,000 – 10,000: ±1.5% |
Phase Angle Measurement | 0 – 360 degrees; Accuracy: ± 1.0 degree) |
Resistance Reading Range | 100 micro-ohms – 30 ohms Accuracy: 2% of reading, ± 1 count, ± 10 micro-ohms |
Insulation Resistance Reading Range | 2 Mega-ohms – 500 Mega-ohms Accuracy: 3% of reading, 500 – 1000 Vdc test voltage |
Display | Back-lit LCD Screen 240 x 128 pixels; 114mm x 64mm Viewable in bright sunlight and low-light levels |
Printer | Built-in 4.5-inch wide thermal printer |
Computer Interfaces | One USB port and Bluetooth wireless interface |
External Data Storage | One USB Flash drive interface port (Flash drive not included) |
PC Software | Windows®-based CT Analysis software is included with purchase price |
Internal Test Record Storage | Stores 140 test records. Each test record may contain up to 10 sets of excitation, resistance and ratio data |
Internal Test Plan Storage | Stores 128 test plans. Each test plan can store 10 excitation test voltage and current settings |
Safety | Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards |
Environment | Operating: -10°C to +50°C (+15°F to +122°F) Storage: -30°C to +70°C (-22°F to +158°F) |
Humidity | 90% RH @ 40°C (104°F) non-condensing |
Altitude | 2,000 m (6,562 ft) to full safety specifications |
Cables | One 20-foot cable set (X1-X5) One 35-foot H cable set Current source cables Insulation test cables Power cord Ground cable A transportation case is included with the purchase price |
Note: Specifications are valid at nominal voltage and ambient temperature of +25˚C (+77˚F).