Specifications |
|
EZCT-2000C Plus
Current Transformer Test Set
|
|
Features | Parameters |
Type | Portable current transformer test set |
Dimensions | 19"W x 13"H x 16"D
(48.3 cm x 33cm x 40.1 cm)
|
Weight | 73 lbs
(33.1 kg)
|
Input Power | 100 ¬ 120 Vac or 200 ¬ 240 Vac (factory pre-set), 50/60 Hz |
Measurement Method | ANSI/IEEE C57.12.90
ANSI/IEEE C57.13.1 standards
|
Output Test Voltages | 0 ¬ 50 Vac @ 10A max
0 ¬ 300 Vac @ 10A max
0 ¬ 500 Vac @ 5A max
0 ¬ 1200 Vac @ 1.2A max
0 ¬ 2000 Vac @ 1A max
|
Current Source | 1 ¬ 20A @ 0 ¬ 15 Vac |
Current Source Display | Test current and current on-time |
Voltage Reading Range | 0 ¬ 2,200 Vac; Accuracy: ±1.0% of reading, ±1 volt |
Current Reading Range | 0 ¬ 10A; Accuracy: ±1.0% of reading, ±0.02A |
Current Ratio Range | 0.8 ¬ 999: 0.1%, 1000 ¬ 1999: 0.3%, 2000 ¬ 5000: 1% |
Phase Angle Measurement | 0 ¬ 360 degrees; Accuracy: ±1.0 degree |
Resistance Reading Range | 100 micro-ohms ¬ 10 ohms; Accuracy: 2% of reading, ±1 count, ±10 micro-ohms |
Insulation Resistance Reading Range | 2 Mega-ohms ¬ 500 Mega-ohms; Accuracy: 3% of reading, 500 ¬ 1000 Vdc test voltage |
Display | Backlit LCD Screen
(240 x 128 pixels; 114mm x 64mm)
Viewable in bright sunlight and low-light levels
|
Printer | Built-in 4.5-inch wide thermal printer |
Computer Interfaces | One USB port and Bluetooth wireless interface |
External Data Storage | One USB Flash drive interface port
(Flash drive not included)
|
PC Software | Windows®-based CT Analysis software is included with purchase price |
Internal Test Record Storage | Stores 140 test records.
Each test record may contain up to 10 sets of excitation, resistance and ratio data
|
Internal Test Plan Storage | Stores 128 test plans.
Each test plan can store 10 excitation test voltage and current settings
|
Safety | Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards |
Environment | Operating: -10°C to +50°C (+15°F to +122°F)
Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity | 90% RH @ 40°C (104°F) non-condensing |
Altitude | 2,000 m (6,562 ft) to full safety specifi cations |
Cables | One 20-foot cable set (X1-X5)
One 35-foot H cable set
Current source cables
Insulation test cables
Power cord
Ground cable
A transportation case is included with the purchase price
|