There are many possible current probe options available from Dranetz to fulfill your current measurement requirements for both Dranetz PX5/4400, Energy Platform, and Encore Series 61000 Monitoring instruments. Many of these current probes connect directly into the PX5/4400, Energy Platform, and Encore Series 61000 instruments. For the Encore Series 61000 a 61MAC input module allows connection of the available current probes to the instrument.
Benefits |
|
Clamp-On | Clamp-on type probes are available to measure as low as 0.1 A to a maximum of 3000 Amps in various ranges.
Also, there are available clamp-on probes that measure both AC and DC currents.
|
Flexible Probes | These type of probes are available in three lengths 24 inches, 36 inches, and 48 inch lengths which allow monitoring currents up to 6000 Amps full scale. |
Specifications |
|
|
|
|
|
|
AC Clamp-On Probes Overview |
|
|
|
|
|
|
Model
Number
| Range | Range | Amplitude Accuracy ± | Phase
Accuracy ±
| Frequency Range | Maximum Conductor Size |
TR2500 | 10A to 500 Arms | 10A to 500 Arms | 1.5% of reading +0.6A | < 4º | 48Hz-1kHz | 30mm dia. |
TR2500A | 10A to 500 Arms | 100A to 500A
10A to 100A
| 1%
2%
| 1.5°
3°
| 40Hz to 5KHz | 50mm dia. |
TR2501 | 100mA to 1.2Arms | 1.2A
100mA
| 1.5%
1.5%
| 1°
2°
| 40Hz to 5KHz | 15mm dia. |
TR2510 | 1A to 10 Arms | 1A to 10 A | 1% | 1.5° | 40Hz to 3 KHz | 20 mm dia. |
TR2510A | 1A to 10Arms | 5A to 10A
1A to 5A
| 1.2%
2%
| 1.5°
1°
| 40Hz to 5KHz | 15mm dia. |
TR2520A | 100A to 3000Arms | 1000A to 3000A
300A to 1000A
100A to 300A
| 0.5%
0.75%
1.5%
| 0.5°
0.75°
1.5°
| 40Hz to 5KHz | 72mm dia.* |
TR2530A | 20A to 300Arms | 50A to 300A
20A to 50A
| 1%
1.5%
| 0.5°
0.6°
| 30Hz to 5KHz | 54mm dia. |
TR2540A | 10A to 1000A | 10A to 100A
1A to 10A
| 1%
2%
| 2.5°
5°
| 40Hz to 10KHz | 15mm dia |
Notes:
* or bus bar
Transient Accuracy: ±10% of Reading, ±0.5% Full scale, ≥10 uSec