配置型號包含以下特性:
Electrical Power TestHipot Testing請參考資源中的資料文檔或查看產品總覽。
如果您想瞭解更多,請 聯繫,我們的團隊將為您提供幫助。
This model replaces the ground breaking and very popular model HVA30. The HVA30 was upgraded to the HVA34 to accommodate the new testing requirements for 25kV rated cables as per the latest revision of IEEE400.2 testing standard.
Arguably the top selling VLF/DC instrument on the market, this instrument has become the standard for testing 25kV rated cables and below. The upgraded model includes an even more powerful output while keeping the same overall weight, physical dimensions, and user interface.
A single piece design, weighting only 44 lbs / 19.5kgs, it is capable of testing up to 120, 000ft / 37km of cable. This is not just a VLF hipot, it also includes a DC hipot, Fault conditioning, Sheath testing, and Vacuum Bottle testing modes all housed in single piece, powerful test instrument.
Key Features |
Test your 25 (Maint), 15, 11, 8, 6.6, 5kV long MV cables |
Weighs only 44lbs / 19.5kg |
Perform tests fully automatically |
Oscilloscope Display of Output Waveform |
Insulation Resistance & Cap. Measurement |
RMS Metering of Current and Voltage |
Output Frequency optimization |
Internal Storage of Test Reports |
Download to PC and / or USB flash drive |
Unlimited duty cycle |
Flashover voltage detection |
Bright backlit LCD display |
Power supply immunity and independence |
Low maintenance, oil-free design |
Benefits | |
Output Modes | VLF Sinewave / Squarewave & DC outputs VLF 24kVrms / 34kVpk output DC ±34kV Cable Jacket / Sheath testing Vacuum Bottle testing |
Safety | Integrated internal discharge of DUT Short circuit detection 12kV power frequency voltage feedback protection Remote interlock “kill switch” and HV status indication |
Specifications | |
HVA34 VLF/DC Hipot Tester | |
Feature | Parameters |
Power Supply/Input Voltage | 110 to 240V AC ±10% (50/60Hz) |
Input Power Requirements | 400VA |
Rated Max Output Voltage | Sinusoidal RMS/Peak: 24kV/34kV Squarewave: 34kV DC: ±34kV |
Rate Max Output Current | Sinusoidal RMS: 10mA DC/Squarewave: 14.5mA |
Output Frequency (default 0.1Hz) | 0.01Hz to 0.1Hz adjustable small increment of 0.01Hz (10 frequencies) |
Frequency Optimization | Yes |
Specifications | |
VLF/DC Hipot Tester | |
Model Overview | |
Model | Description |
With Integrated Tan Delta | |
HVA28TD | Output Voltage: 29kV, 21kVrms, Load: 0.5µF @ 0.1Hz @ 20kVrms, Weight: 31lbs/14 kg |
HVA34TD | Output Voltage: 34kV, 24kVrms Load: 1.5µF @ 0.1Hz @ 24kVrms, Weight: 44lbs/20 kg |
HVA45TD | Output Voltage: 45kV, 32.3kVrms Load: 1.0µF @ 0.1Hz @ 32kVrms, Weight: 86lbs/39 kg |
VLF/DC Only - HVA Series | |
HVA34 | Output Voltage: 34kV, 24kVrms Load: 0.5µF @ 0.1Hz @ 24kVrms, Weight: 44lbs/20 kg |
HVA30-7 | Output Voltage: 34kV, 24kVrms Load: 6.0µF @ 0.1Hz @ 24kVrms, Weight: 125lbs/57 kg |
HVA60 | Output Voltage: 62kV, 44kVrms Load: 1.0µF @ 0.1Hz @ 44kVrms, Weight: 126lbs/57 kg |
HVA90 | Output Voltage: 90kV, 64kVrms Load: 1.0µF @ 0.1Hz @ 64kVrms, Weight: 280lbs/127 kg |
HVA120 | Output Voltage: 120kV, 85kVrms Load: 0.5µF @ 0.1Hz @ 85kVrms, Weight: 436lbs/198 kg |
HVA200 | Output Voltage: 200kV, 141kVrms Load: 0.6µF @ 0.1Hz @ 141kVrms, Weight: 2,094lbs/950 kg |