| Specifications |
|
EZCT-2000C
Current Transformer Test Set
|
|
| Features | Parameters |
| Type | Portable current-transformer test set |
| Dimensions | 19″W x 13″H x 16″D
(48.3 cm x 33cm x 40.1 cm)
|
| Weight | 73 lbs
(33.1 kg)
|
| Input Power | 100 – 120 Vac
or
200 – 240 Vac (factory pre-set), 50/60 Hz
|
| Measurement Method | IEC 60044-1
IEC 61869
ANSI/IEEE C57.13.1
ANSI/IEEE C57.12.90
|
| Test Output Voltages | 0 – 50 Vac @ 10A max
0 – 300 Vac @ 10A max
0 – 500 Vac @ 5A max
0 – 1200 Vac @ 1.2A max
0 – 2000 Vac @ 1A max
|
| Current Source | 1 – 20A @ 0 – 15 Vac |
| Current Source Display | Test current and current on-time |
| Voltage Reading Range | 0 – 2,200 Vac
Accuracy: ±1.0% of reading, ±1 V
|
| Current Reading Range | 0 – 10A
Accuracy: ±1.0% of reading, ±0.02A
|
| CT Current Ratio Range | 0.8 – 999: ±0.1%
1000 – 1999: ±0.3%
2,000 – 4,999: ±1%
5,000 – 10,000: ±1.5%
|
| Phase Angle Measurement | 0 – 360 degrees; Accuracy: ± 1.0 degree) |
| Resistance Reading Range | 100 micro-ohms – 30 ohms
Accuracy: 2% of reading, ± 1 count, ± 10 micro-ohms
|
| Insulation Resistance Reading Range | 2 Mega-ohms – 500 Mega-ohms
Accuracy: 3% of reading, 500 – 1000 Vdc test voltage
|
| Display | Back-lit LCD Screen
240 x 128 pixels; 114mm x 64mm
Viewable in bright sunlight and low-light levels
|
| Printer | Built-in 4.5-inch wide thermal printer |
| Computer Interfaces | One USB port and Bluetooth wireless interface |
| External Data Storage | One USB Flash drive interface port
(Flash drive not included)
|
| PC Software | Windows®-based CT Analysis software is included with purchase price |
| Internal Test Record Storage | Stores 140 test records.
Each test record may contain up to 10 sets of excitation, resistance and ratio data
|
| Internal Test Plan Storage | Stores 128 test plans.
Each test plan can store 10 excitation test voltage and current settings
|
| Safety | Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards |
| Environment | Operating: -10°C to +50°C (+15°F to +122°F)
Storage: -30°C to +70°C (-22°F to +158°F)
|
| Humidity | 90% RH @ 40°C (104°F) non-condensing |
| Altitude | 2,000 m (6,562 ft) to full safety specifications |
| Cables | One 20-foot cable set (X1-X5)
One 35-foot H cable set
Current source cables
Insulation test cables
Power cord
Ground cable
A transportation case is included with the purchase price
|