I modelli configurati contengono le seguenti caratteristiche:
Electrical Power TestHipot TestingUtilizza "Preventivo rapido" e ti contatteremo per fornirti un preventivo per le tue esigenze.
Puoi anche contattarci, se preferisci, e i nostri esperti ti guideranno a trovare la giusta applicazione e soluzione di acquisto per questo prodotto.
Siamo spiacenti, al momento non abbiamo informazioni sulle specifiche chiave per questo prodotto disponibile online.
Per maggiori informazioni, ti preghiamo di contattarci e un membro del nostro team ti assisterà.
The TD60-MC system uses wireless Bluetooth technology and has an extremely simple test set up making field testing a breeze. Compared to other large and bulky TD systems on the market that require several connections, the TD60-MC requires very few connections and interfaces easily with the HVA60 using a multi-connector (MC).
The TD60-MC is a great tool to trend cable data overtime to show gradual degradation decreasing operational risk. Defective and/or degraded terminations and splices, water treeing, concentric neutral wire corrosion, and installation defects can be detected with this instrument.
The TD60-MC is designed to work with the HVA60 VLF system and is therefore capable of performing diagnostic tests on 35kV cables and below. The unit comes in a custom case with rollers and a convenient, pull-out handle for easy transportation. The unit is supplied with host of accessories including corona protection, jumper cables, ground cable, D Type batteries, D Battery Charger etc.
Key Features |
Perform advanced diagnostics on MV Cables according to IEEE400 and 400.2 |
Suitable for testing 35kV cables and below |
Wireless Bluetooth Connection |
Minimum connection hookups |
Accurate 1E-5 Resolution! |
Excellent, easy to use TD reporting |
Supplied with Free TD control center Software and FW upgrades |
Local LED indication for TD value range |
Leakage Current Guard Protection |
Sleep mode saves battery life |
Uses universal C-type batteries |
Supplied in rugged transport case with all accessories. |
Applications |
XLPE |
EPR |
PE |
PILC |
Capacitors |
Transformer |
Rotating machines |
Detecting water trees |
Detecting water degradation |
Specifications | ||||
TD60-MC Diagnostic Measurement System; Tan Delta-60MC | ||||
Model Overview | ||||
Model: | TD30 | TD60-MC | TD90-MC | TD120-MC |
Ordering Information | 700 003 | 706 003 | 709 003 | 712 003 |
Power Supply | 2 C Type Batteries | 2 C Type Batteries | 2 C Type Batteries | 2 C Type Batteries |
Rated Operating Voltage | RMS: 1-23kV Peak: 33kV | RMS: 1-44kV Peak: 62kV | RMS: 1-64kV Peak: 90kV | RMS: 1-85kV Peak: 120kV |
Voltage Measurement | Resolution: 0.1kV Accuracy: 1% (of reading) | Resolution: 0.1kV Accuracy: 1% (of reading) | Resolution: 0.1kV Accuracy: 1% (of reading) | Resolution: 0.1kV Accuracy: 1% (of reading) |
Current Measurement | Resolution: 1µA Accuracy: 1% (of reading) | Resolution: 1µA Accuracy: 1% (of reading) | Resolution: 1µA Accuracy: 1% (of reading) | Resolution: 1µA Accuracy: 1% (of reading) |
Frequency Measurement | Range: 0.01 to 0.1Hz Resolution: 0.01Hz | Range: 0.01 to 0.1Hz Resolution: 0.01Hz | Range: 0.01 to 0.1Hz Resolution: 0.01Hz | Range: 0.01 to 0.1Hz Resolution: 0.01Hz |
Tan Delta/ Dissipation Factor Measurement | Resolution: 1 x 10 -5 Accuracy >15nF: ±1 x 10 -4 Accuracy <15nF: ±3 x 10 -4 | Resolution: 1 x 10 -5 Accuracy >15nF: ±1 x 10 -4 Accuracy <15nF: ±3 x 10 -4 | Resolution: 1 x 10 -5 Accuracy >15nF: ±1 x 10 -4 Accuracy <15nF: ±3 x 10 -4 | Resolution: 1 x 10 -5 Accuracy >15nF: ±1 x 10 -4 Accuracy <15nF: ±3 x 10 -4 |
Load Range | 0.5nF to 10 µF | 0.5nF to 10 µF | 0.5nF to 10 µF | 0.5nF to 10 µF |
Weight | 7 lbs / 3 kgs | 11 lbs / 5 kgs | 24 lbs / 11 kgs | 35 lbs / 16 kgs |
Dimensions (LxWxH) | 9.5" x 3.5" 240 x 85mm | 12" x 11" x 25" 300x280x640mm | 12" x 11" x 31" 300x280x790mm | 12" x 11" x 31" 300x280x790mm |
Computer Interface | Bluetooth™ | Bluetooth™ | Bluetooth™ | Bluetooth™ |
Accessories Included | Integrated HV and Grounding Cable Bluetooth USB Dongle TD Control Center Software Operating Manual Corona Protection | Integrated HV and Grounding Cable Bluetooth USB Dongle TD Control Center Software Operating Manual Corona Protection | Integrated HV and Grounding Cable Bluetooth USB Dongle TD Control Center Software Operating Manual Corona Protection | Integrated HV and Grounding Cable Bluetooth USB Dongle TD Control Center Software Operating Manual Corona Protection |
Standards | Shock: IEC68-2-27 Vibration: IEC68-2-6 EMC: IEC6100-4-2 IEC6100-4-4 EN55011 Safety: EN60950 EN50191 EN61010-1 | Shock: IEC68-2-27 Vibration: IEC68-2-6 EMC: IEC6100-4-2 IEC6100-4-4 EN55011 Safety: EN60950 EN50191 EN61010-1 | Shock: IEC68-2-27 Vibration: IEC68-2-6 EMC: IEC6100-4-2 IEC6100-4-4 EN55011 Safety: EN60950 EN50191 EN61010-1 | Shock: IEC68-2-27 Vibration: IEC68-2-6 EMC: IEC6100-4-2 IEC6100-4-4 EN55011 Safety: EN60950 EN50191 EN61010-1 |
Environmental | Storage: -13°F to 158°F/ -25°C to 70°C Operating: 23°F to 113°F/ -5°C to +45°C Humidity: 80% RH non-condensing | Storage: -13°F to 158°F/ -25°C to 70°C Operating: 23°F to 113°F/ -5°C to +45°C Humidity: 80% RH non-condensing | Storage: -13°F to 158°F/ -25°C to 70°C Operating: 23°F to 113°F/ -5°C to +45°C Humidity: 80% RH non-condensing | Storage: -13°F to 158°F/ -25°C to 70°C Operating: 23°F to 113°F/ -5°C to +45°C Humidity: 5 to 85% RH non-condensing |