配置型号包含以下特性:
Electrical & Power QualityTransformer and Motor Testing请参考资源中的资料文档或查看产品总览。
如果您想了解更多,请 联系,我们的团队将为您提供帮助。
The Megger MWA300 and 330A Transformer Winding Analyzers are here to offer you a faster, more efficient testing device through combining TTR and resistance testing in a single unit. This advanced 3-phase transformer test system provides complete ratio, phase and winding resistance measurements with only one 3-phase lead-set connection. What’s more, it offers portability, a reduced set-up time and increased job safety.
Once connected, the MWA300 performs DC resistance measurements on all high- and low-side windings without reconnection. It has an 8-terminal/6-winding resistance measurement capability and doesn’t need any inter-connected boxes, allowing you to test all 6 windings without having to disconnect and reconnect leads.
The MWA300 series saves you even more time by using a single software platform, PowerDB, which means you only need one set-up and one easy-to-use test form. The MWA300 series can be used effectively test power transformers, distribution transformers, CTs and VTs, and motors and generators.
The MWA330A comes equipped with a built-in computer that has a 305 mm (12 in) color display and touch-screen interface. The computer is designed to control the unit and it can store up to 100, 000 data sets.
Key Features |
Combines TTR and resistance testing in one box - faster, more efficient testing |
55% smaller, 40% lighter than individual instruments |
Only one set of leads required - lighter, smaller and less expensive |
One test form - easier, faster to complete |
Built-in demagnetization |
Benefits | |
The following tests are easily performed with a single instrument | 3-phase turns ratio 3-phase winding resistance OLTC continuity (make-before-break) 3 phase core demagnetization Magnetic balance / flux distribution Excitation current Polarity and phase angle deviation Auto vector detection Heat-run test |
Specifications | |
MWA3xx Three-Phase Ratio and Winding Resistance Analyzer | |
Feature | Parameter |
Input Power | MWA3xx: 108 to 132 V, (207 to 253 V*), 58 - 62 Hz, 660 VA MWA3XX-47: 207 to 253 V, (108 to 132 V*), 48 - 52 Hz, 660 VA |
Internal Data Storage | MWA330A (built-in computer): up to 100,000 data sets (built-in computer) |
Communication/Control Software | MWA3xx: PowerDB Lite MWA330A: Controlled via built-in industrial PC or external customer PC. The MWA330A’s internal computer is designed to control a limited number of Megger instruments including the DELTA4000 as well as the Megger S1 and MIT Series DC insulation testers. |
Environmental | Operating: -10⁰ C to +50⁰ C (14⁰ F to 122⁰ F) Storage: -30⁰ C to +70⁰ C(-22⁰ F to +158⁰ F) Relative Humidity: 0-90% non-condensing |
Case | Ruggedized case (metal/plastic trim) with removable lid and soft-side pouch with carrying strap |
Safety/EMC/Vibration | Conforms to the requirements of: IEC 61010-1:2010 ASTMD999.75, IEC 61326-1:2012* (both emissions and immunity) |
Dimensions | 290 x 290 x 460 mm 11 x 11 x 18 in does not include handles |
Weight | Standard Unit: 14.5 kg 32 lbs |
Transformer Winding Phase Relationship | ANSI C57.12.70-1978 CEI/IEC 76-1:1993 and Publication 616:1978 AS-2374, Part 4-1982 (Australian Standard) DC Specifications (Winding resistance, LTC/continuity, core demagnetization, heat-run) |
Excitation Current Specifications | Range and Accuracy: 0 to 500 mA, 3 digit resolution, ±(2% of reading + 1 digit) |
AC Specifications (Turns Ratio, Winding Balance) | Range and Turns Ratio Accuracy: 8 V AC: ±0.1% (0.8 to 2000) ±0.25% (2001 to 4000) ±0.35% (4001 to 8000) 40 V AC: ±0.1% (0.8 to 2000) ±0.15% (2001 to 4000) ±0.3% (4001 to 10,000) ±0.35% (10,001 to 25,000) 80 V AC: ±0.1% (0.8 to 2000) ±0.15% (2001 to 4000) ±0.25% (4001 to 10,000) ±0.30% (10,001 to 45,000) |
Phase Specifications | Input voltages: 8, 40, and 80 V AC Range and Accuracy: ±90 degrees, 2 decimal points for the degree display, or for the centi-radian display Accuracy: ±3 minutes (from 0.8:1 – 2,000:1) |
Note:
* Input fuse change required - 6.3A fuse for 120 V nominal and 4.0A fuse for 230 V nominal line input.
Specifications | |
MWA 3xx Series 3-Phase Ratio and Winding Resistance Analyzer | |
Model Overview | |
Model | Description |
Externally controlled Model MWA 300 Series | |
MWA300 | 3-Phase Winding Analyzer, remote control only, nominal 120 V, 60 Hz* |
MWA300-47 | 3-Phase Winding Analyzer, remote control only, nominal 230 V, 50 Hz* |
Built-in Computer Model MWA 330A Series | |
MWA330A | 3-Phase Winding Analyzer, on board industrial computer with 305 mm (12 in.) touch screen nominal 120 V, 60Hz* |
MWA330A-47 | 3-Phase Winding Analyzer, on board industrial computer with 305 mm (12 in.) touch screen nominal 230 V, 50Hz* |
Included Accessories | AC power cord (IEC60320-C13 to US Standard) (MWA300/330A only) AC power cord (IEC60320-C13 to EU Standard) AC power cord (to UK Standard) (MWA300-47 and MWA330A-47 only) USB 2.0 standard type A to B Cable 2 m (7 ft) USB memory stick contains: user guide, PowerDB Lite, software related documents Quick Guide, EN/ES/DE/FR Ground lead, 9 m (30 ft) Canvas carrying bag |
Optional Accessories (3-phase, 4-wire shielded test lead sets compatible with MTO3xx, MWA3xx & TTR3xx series instruments (up to 10A max), complete with color-coded Kelvin clamps) | |
2008-30-KIT | 3-phase universal, 9 m (30 ft) H & X |
2008-60-KIT | 3-phase universal, 18 m (60 ft) H & X |
2008-100-KIT | 3-phase universal, 30 m (100 ft) H & X |
2008-113-30 | 3-phase universal, 9 m (30 ft) H |
2008-114-30 | 3-phase universal, 9 m (30 ft) X |
2008-113-60 | 3-phase universal, 18 m (60 ft) H |
2008-114-60 | 3-phase universal, 18 m (60 ft) X |
2008-113-100 | 3-phase universal, 30 m (100 ft) H |
2008-114-100 | 3-phase universal, 30 m (100 ft) X |
36486-7 | 3-phase universal,10 m (33 ft) X, Extension |
36486-8 | 3-phase universal, 10 m (33 ft) H, Extension |
36486-9 | 3-phase universal, 10 m (33 ft) H & X Extension |
1007-502 | Remote tap controller, manual operation, model RTC-1, complete with quick guide, and red/black/white (total 3) alligator clips |
1004-639 | HV strobe c/w 18 m (60 ft) lead |
1006-512-2 | Verification resistor, 10A,10 m ohms |
2005-115 | Foam lined transit case |
Y550055 | Turns ratio calibration standard |
2001-766 | Soft padded carrying case |
Note:
* Please refer to Input Power under Specifications above for details.