配置型号包含以下特性:
Electrical & Power QualitySwitchgear / Relay Testing请参考资源中的资料文档或查看产品总览。
如果您想了解更多,请 联系,我们的团队将为您提供帮助。
Moisture is the most important criteria for the determination of the gas quality. This device has been designed specifically for SF6 moisture measurements. It shows a higher resistance against contamination and SF6 decomposition products than conventional moisture sensors and even minimizes the usual long-time drift.
The integrated electronic flow meter supports the minimization of the gas sample quantity and works independently of its position, which is the optimum for gas sampling from a circuit breaker. Pressure and temperature influences on the measuring result can be excluded. It is a reliable, indispensible instrument for SF6 gas handling.
The 3-037-R002 moisture measuring device was designed from the ground up, to be used on arced SF6 . Unlike conventional multigas hygrometers, the 3-037 is specifically calibrated for the unique characteristics (i.e. densities, molecular weights, and acidity) of faulted SF6 . Not only is the device consistently more accurate and reliable, but the typical long-term drift (and subsequent need for factory recalibration) associated with non gas-specific devices is all but eliminated.
The exclusive DILO sensor measures SF6 at atmospheric pressure which removes pressure and temperature variables from moisture readings. Additionally, the electronic flow meter not only reduces the sample to a trickle, but the orientation of the device is no longer relevant – making the 3-037 far more suitable for on-site testing. All readings are displayed in parts per million by volume (PPMv).
Benefits |
Indication in °C dew point, quick conversion into ppm values |
Measurement is possible under atmospheric or plant pressure |
Mains operation or operation by NiMH accumulators |
Key Features |
Moisture measuring device with digital display |
2 precision regulation valves |
Electronic flow meter |
Powered by AC or NiMH batteries (internal charger) |
2 meter long connecting hose with couplings DN 8 and DN 20 |
Rugged case with handle |
2 meter long power cable (for AC use) |
Aluminum carrying case |
2 operating instructions in: German, English, and/or French |
Specifications | |
Moisture Measuring Device SF6 | |
Feature | Parameter |
Dimensions (W x H x D) | 10 “ x 5.1” x 13.6” 254 x 130 x 345 mm |
Weight | 6.2 lbs 2.8 kg |
Measuring Range | 41PPMv – 10,000PPMv |
Measuring Accuracy | ±2°C ±4°F |
Max. Input Pressure | pe10 bar 145 PSIG |
Operating Temperature | 0-40°C 32°F - +104°F |
Operating Voltage | 100 – 240V, 50/60 Hz |
Flow Rate | 1 liter of SF6 /min |