The TM1800 is the instrument platform for circuit breaker maintenance, based on more than 20 years’ experience of over 4,000 delivered breaker analysers. The modular construction makes it possible to configure the TM1800 for measurements on all known types of circuit breakers in operation in today’s power world.
The robust design contains powerful technology that streamlines circuit breaker testing. Sophisticated measurement modules enable great time savings as many parameters can be measured simultaneously, eliminating the need for new setup each time. The patented DualGround™ testing using the DCM module makes the testing safe and time saving by keeping the circuit breaker grounded on both sides throughout the test. The DCM module uses a measuring technology called Dynamic Capacitive Measurement.
The modularized design makes it very flexible to user needs and enables reconfiguration for new demands and upgrade with new functionality. You can configure TM1800 to a complete test set tailor made for your specific needs. The software, CABA Local, guides you to efficient circuit breaker testing. All inputs and outputs on the TM1800 and the modules are designed to withstand the harsh environment in high-voltage substations and industrial environments.
With built-in protection circuits and software-designed protection the TM1800 has a good guard to influences and even failures caused by over-voltages generated in the environment.
The HDD module is a part of the basic unit and contains the hard drive with all data and software setup. It can easily be removed and changed.
Key Features |
Modular based design - user configurable TM1800 from nine different modules |
Eight user configurable slots for modules |
Temperature sensor connection |
Trig inputs and outputs |
Outputs for warning signal and DRM |
Built in PC with CABA Local software - advanced testing with predefined breaker test plans (templates), onsite measurement view and analysis |
DualGround™ testing using DCM module - increased safety with both sides of breaker grounded |
Fast and easy testing - Select-Connect-Inspect workflow and high level user interface |
Graphical results for quick interpretation - timing and motion measurements, coil currents |
USB and Ethernet communication interface - for quick back up, LAN connection and printer options |
CABA Win - for advanced data analysis, database interface and common test data archive |
Benefits |
|
Control Module | Generates the selected circuit breaker operation sequences accurate and bounce-less.
The Control module, with 9 analog channels (3 U + 6 I), also measures important parameters during the test. Coil current, control voltage, coil resistance and auxiliary contact timing are automatically measured for each phase without any additional test lead connections.
- Three independent contact functions per module
- Pre-programmed sequences C, O, C–O, O–C, O–C–O
- Timing of a and b auxiliary contacts
- Coil current (max 30 A), voltage and resistance
|
Timing M/R Module | The Timing M/R module uses one hook-up for testing all the important timing parameters of a contact without the need of reconnection or special set-ups.
One timing M/R module, with 12 analog channels (6 U + 6 I), will time up to six main plus six PIR contacts and measure values of the Pre-Insertion Resistors.
With the same hook-up Timing M/R can also perform static and dynamic resistance measurements (using SDRM202).
The Timing M/R module is using patented Active Interference Suppression to obtain correct timing and accurate PIR values regardless of interference in high voltage substations.
The channels are also used for voltage measurement during SRM and DRM test.
- Six inputs per module
- High resolution 15 μV and up to 40 kHz sampling
- Main and parallel resistor contact timing
- Resistance value of parallel resistors
|
DCM Module | The DCM module enables DualGround testing.
This increases safety and also makes testing easier. Each pair of a Timing M/R and DCM module provides up to six channels.
Each channel requires a special DCM cable with integrated electronics.
The TM1800 system can be equipped with multiple DCM and Timing M/R module pairs that enable timing measurement on up to 18 contacts.
- Six channels per module
- Timing test using DualGround
- Safe, fast and easy testing
- Two breaks per phase
- GIS breaker testing
|
Analog Module | The Analog module measures any analog entity from a transducer mounted on a circuit breaker.
It enables measurements of motion, speed, current, voltage, pressure, vibration etc.
A motion measurement of a circuit breaker is simple thanks to the flexible and easy to use interface. Universal transducers, specialized transducers and conversion tables are available for several circuit breakers. See the accessory section.
- Three channels per module
- Supports industrial analog transducers
- Insulated channels, measure up to 250 V whithout volt. div.
- High resolution 0.3 mV, sampling rate 40 kHz
|
Digital Module | With digital transducers motion and other measurements become even more accurate, faster and easier.
The Digital module enables use of incremental rotary or linear transducers, for measuring e.g. motion, velocity and damping characteristics of circuit breakers.
- Six channels per module
- Incremental transducers with RS422 connection
- Up to ±32000 pulses resolution
- Up to 20 kHz sampling
|
Timing AUX Module | Expands the TM1800 system with timing inputs for measuring any auxiliary contact on the circuit breaker.
It measures timing, polarity insensitive, of both dry and wet contacts for example timing of spring charging motor, anti-pump relay etc.
- Six channels per module
- Polarity insensitive
- Dry and wet auxiliary contacts
|
Printer Module | The Printer module offers a convenient and practical way of making printouts of test results in the field.
The printouts contain both numerical and graphical results and printer templates delivered preinstalled in the TM1800 are easy to adapt to suit specific needs for a clear and complete report of all tested parameters.
- Thermal printer sensitive line dot method- Paper width 114 mm (4")
- Printing speed 50 mm/s (400 dot lines/s)
|
HDD Module | The HDD module is a part of the Basic unit.
Storage of all set-up, user customization and measurement data is done in the HDD module.
The module is easily replaced e.g. when different users are sharing one TM1800 and want individual setups, data and configurations.
- Change set-up, user customization, measurement data by changing HDD module
- Easy to remove during transportation
|
Specifications |
|
TM1800
Circuit Breaker Analyzer
|
|
Feature | Parameter |
Mains Input (nominal) | 100 – 240 V AC, 50/60 Hz |
Power Consumption | 250 VA (max) |
Operating Temperature | -20°C to +50°C
(-4°F to +122°F)
|
Storage and Transport Temperature | -55°C to +70°C
(-67°F to +158°F)
|
Humidity | 5% – 95% RH, non-condensing |
CE- Marking | EMC 2004/108/EC
LVD 2006/95/EC
|
Dimensions | 515x173x452 mm
(20.3”x6.8”x17.8”)
|
Weight | 11.5 kg
(25.4 lbs)
|
Specifications |
|
TM1800
Circuit Breaker Analyzer
|
|
Model Overview |
|
Cat. Number | Description |
CG-19090 | TM1800 Basic Unit
Complete with:
HDD module
CABA Local
Transport case
USB Memory
|
CG-19030 | Control Module (3 independent contacts)
Including:
1 cable set, 5 m (16 ft)
|
CG-19080 | Timing M/R Module (6 channels + 6 PIR)
Including:
3 cable sets, 5 m (16 ft) total length, 2 m (6.5 ft) spread
|
CG-19190 | DCM Module
Including:
3 DCM-cables, 10 m (33 ft)
|
CG-19192 | DCM Module
Including:
6 DCM-cables, 10 m (33 ft)
|
CG-19000 | Analog Module (3 channels)
Including: 3 cable sets, 10 m (33 ft)
|
CG-19040 | Digital Module (6 channels) |
CG-19060 | Timing Aux Module (6 channels)
Including:
3 cable sets, 5 m
|
CG-19050 | Printer Module
Including:
Paper spool
|
Specifications |
|
TM1800
Circuit Breaker Analyzer
|
|
Configuration Overview |
|
Cat. Number | Description |
CG-19290 | TM1800 Standard
Including:
TM1800 Basic Unit x1 (CG-19090)
TM1800 Control Module x1 (CG-19030)
TM1800 Timing M/R Module x1 (CG-19080)
TM1800 Analog Module x1 (CG-19000)
CABA Win - TM1800 x1 (CG-8000X)
|
CG-19292 | TM1800 Standard – for DualGround Testing
Including:
TM1800 Basic Unit x1 (CG-19090)
TM1800 Control Module x1 (CG-19030)
TM1800 Timing M/R Module x1 (CG-19080)
TM1800 DCM Module x1 (CG-19192)
TM1800 Analog Module x1 (CG-19000)
CABA Win - TM1800 x1 (CG-8000X)
|
CG-19294 | TM1800 Expert
Including:
TM1800 Basic Unit x1 (CG-19090)
TM1800 Control Module x1 (CG-19030)
TM1800 Timing M/R Module x1 (CG-19080)
TM1800 Analog Module x1 (CG-19000)
TM1800 Timing AUX Module x1 (CG-19060)
CABA Win - TM1800 x1 (CG-8000X)
|
CG-19296 | TM1800 Expert – for DualGround Testing
Including:
TM1800 Basic Unit x1 (CG-19090)
TM1800 Control Module x1 (CG-19030)
TM1800 Timing M/R Module x1 (CG-19080)
TM1800 DCM Module x1 (CG-19192)
TM1800 Analog Module x1 (CG-19000)
TM1800 Timing AUX Module x1 (CG-19060)
CABA Win - TM1800 x1 (CG-8000X)
|