Power Demand Analyzer w/Analog Output

 
browse
Part NumberIncluded Options
Rent/Lease   Buy Used
HIO-3169-21 
Catalog Description

Hioki 3169-21

 HIO-3169-21 Power Demand Analyzer w/Analog Output

Measure up to two 3-phase, 3-wire systems (displays voltage and current for
three lines).
Measure up to four single-phase, 2-wire systems.
5 A to 5000 A range.
Compact and light weight.
PC card data storage.
Power recording for individual waveforms.
Simultaneous recording of demand values and harmonics.

Basic Specifications:

Measurement line type - Single-phase 2-wire, single-phase 3-wire, three-phase
3-wire, and three-phase 4-wire systems (50/60 Hz)

Number of systems that can be measured (for systems that share the same
voltage):
Single-phase:1P2W 4 systems
1P3W 2 systems
Three-phase:3P3W2M (measures the voltage and current for two lines) 2 systems
3P3W3M (measures the voltage and current for all three lines) 1
systems
3P4W (measures the voltage and current for three lines) 1 system
3P4W4I (measures the voltage for three lines and the current for
four lines) 1 system

Measurement item - Voltage, current, active power, reactive power, apparent
power, power factor, integrated value, frequency, harmonics

Measurement range:
Voltage: 150 V to 600 V, 3 ranges
Current (When using 9660):5 A to 100 A, 4 ranges
Current (When using 9661): 5 A to 500 A, 5 ranges
Current (When using 9669): 100 A to 1 kA, 3 ranges
Current (When using 9667): 500 A / 5 kA, 2 ranges
Current (When using 9694): 0.5 A to 5 A, 3 ranges
Power: 75 W to 9 MW, 108 combination patterns

Basic accuracy - +/-0.2% rdg. +/-0.1% f.s. + clamp-on sensor accuracy (active
power, at 45 to 66 Hz)

Clamp sensor accuracy:
9660 (rated for 100 A): +/-0.3% rdg. +/-0.02% f.s.
9661 (rated for 500 A): +/-0.3% rdg. +/-0.01% f.s.
9669 (rated for 1000 A): +/-1.0% rdg. +/-0.01% f.s.
9667 (rated for 5000 A): +/-2.0% rdg. +/-1.5 mV
9694 (rated for 5 A): +/-0.3% rdg. +/-0.02% f.s.
* f.s. is the sensor's rated primary current value.

Frequency characteristic - Fundamental waveforms up to the 50th order +/-3%
f.s. + measurement accuracy (of a 45- to 66-Hz fundamental waveform)

Other functions:
* PC card (1 slot, PC Card Standerd-compliant Type II, Flash ATA card type),
(9726/ 9727/ 9728 PC card, 128MB to 512MB)
* RS-232C (Printer or PC connected to an RS-232C interface),
* D/A output (3169-21 only, 4 channels),
* External I/O

Display update rate - Approx. every 0.5 seconds (except when using a PC card
while accessing the internal memory, or when performing RS-232C
communications)

Power supply voltage rating - 100 to 240 V AC, 50/60 Hz

Dimensions and weight - 210W x 160H x 60D mm +/-5 mm (excluding protrusions),
1.2 kg +/-100 g (3169-20, 3169-21)

Accessories - voltage cord set 9438-03 (1) (1 cord each of black, red, yellow,
and blue), voltage cord (1), power cord (1), input cord label (1), operating
manuals (2) (Advanced edition and Quick Start Guide), CD-R (1) (Advanced
edition and RS-232C interface operating manuals), connection cable 9441 (1)
(for the 3169-21 only)
LengthWidthHeightShip Wt 
8.27 " 6.3 " 2.36 " 4 lb  
    
N/A Currently not available for sale used