Home >> Products >> FLU-43B
 
Fluke Mfg Co 43B
Other Configurations. Call our experienced Sales Staff.
 

Fluke Mfg Co 43B

3PH Power Quality Analyzer

 
browse
Part NumberIncluded Options
Rent/Lease   Buy Used
FLU-43B 
Catalog Description

Fluke Mfg Co 43B


3PH Power Quality Analyzer Handheld
Ranges: 5V, 50V, 500V, 1250V True RMS AC+DC
Accuracy: +/-1% +10 counts
Frequency: 10Hz to 15kHz
Accuracy: +/- .5% +2 counts
Volt/Amps/Hertz
Display

Power:Watts, VA, VAR Reactive Power 1-phase and
3-phase, 3 conductor balanced loads
Ranges: 250 W, 2.50 kW, 25.0 kW, 250 kW, 2.50 MW,
25 MW, 250 MW, 625 MW, 1.56 GW
Accuracy: (2% + 6 counts) Total Power, kA,
(4% + 4 counts) Fundamental power
Accuracy: (1% +10 counts)
PF Power Factor:
Ranges: 0.00 to 1.00
Accuracy: 0.04 to 15.0 KHz
Accuracy: (0.5% + 2 counts)
PF Displacement Power Factor
Range: 0.00 to 0.25 Not specified,
0.25 to 0.90 0.04, 0.90 to 1.00 0.03
Accuracy: (5% + 1 count)
Hz frequency fundamental
Range: 40.0 to 70.0 Hz
Accuracy: (0.5% + 2 counts)
Harmonics:Volts, Amps, Watts:
Fundamental:
V,A (3% + 2 counts), W (5% + 2 counts)
Range: 2 to 31st Harmonic
Accuracy: V,A (5% + 3 counts), W (10% + 10 counts)
Range: 32 to 51st Harmonic
Accuracy: V,A (15% + 5 counts), W (30% + 5 counts)

The AC adapters for the  FLU-43B units can not be set to 230VAC input.
The AC adapter with the unit (PM8907/803) is 120V input only.
To operate the 43B on 230V power you would need a PM8907/801 AC adpter from
FLUKE.
The output of the adapter needs to be 15VDC, 300mA with the center contact
negative.
LengthWidthHeightShip Wt 
9.2 " 3.9 " 2.5 " 14 lb  
    
N/A Currently not available for sale used
Need Configuration Assistance? Call our experienced Sales Staff.