Home >> Products >> DRN-PX5-400
 
Other Configurations. Call our experienced Sales Staff.
 

Dranetz PX5-400

PowerXplorer 400Hz Power Analyzer Mainframe

 
browse
Part NumberIncluded Options
Rent/Lease   Buy Used
DRN-PX5-400/4GB/CALEM/CASE/4GB Compact Flash Memory/4ea CA4300LEM Adaptors/Soft Carry Case
Catalog Description

Dranetz PX5-400



 DRN-PX5-400 fully integrated Power Quality Analyzer Mainframe. No TaskCard
required. Same specifications as the  DRN-PX5. See differences described
below:
Model-PX5-400 performs measurements for 400Hz power frequency systems.
Note that the PX5-400 will also monitor at 50/60Hz. The user needs to set the
default frequency to either 400Hz, 60Hz, or 50Hz, depending on the
application.When operating at 400Hz, RMS calculations are made on a cycle-by
cycle basis with 1 cycle step; whereas at 50/60Hz mode, it steps at 1/2Hz.
Also, the PX5-400 does not calculate the IEEE 1459 power parameters, as well
as flicker, which are NOT defined at 400Hz.
4 Voltage Inputs- 1-600 Vrms, AC/DC, 0.1% rdg + 0.05% FS; 256 samples/cycle.
16-bit ADC.
DC recording requires the use of Hall Effect CT's.Also see  DRN-PR150/SP2
4 Current Inputs; CT's required. 1-6000A CT dependent.
AC/DC, 0.1% rdg +CT's.
256 samples/cycle.
1MHz High speed sampling, 14-bit ADC.
Frequency Range: 15-20Hz/45-65Hz/350-450Hz.

Compliance to:
IEEE 1159, IEC 61000-4-30 A, EN 50160.

Power and Energy Measurements:
W, VA, VAR, TPF, DPF, Demand, Energy.
IEEE 1459 Distorted and Unbalanced Parameters.
Harmonics/Interharmonics per IEC 61000-4-7.
Harmonics and Interharmonics to 63rd.
Flicker per IEC 61000-4-15.

Software required for data transfer. Also see Dranview Software  DRN-DVPX5.
For flash card reader also see  DRN-FLASHREADER-USB.

Current Transformers Required. 1 per channel as needed.
No adaptor required for DRN-TR-25xx.  DRN-CA4300 required for DRN-TR-20xx
series.
See the following for available current transformers:

Current Transformer current ratings:
 DRN-TR2500 10A to 500A RMS 48HZ to 3kHz max conductor size 1.8in to 2.5in.
 DRN-TR2510 1A to 10A RMS max conductor size 0.47in.
 DRN-TR2520 300A to 3000A RMS max conductor size 2.56in.
 DRN-TR2021 1A to 30A RMS 48Hz to 10kHz max conductor size 0.47in.
 DRN-TR2019B 50A to 300A RMS 45Hz to 50kHz max conductor size 2.0in.
DRN-TR2022 10A to 1000A RMS 45Hz to 10kHz max conductor size 2.0in.
 DRN-TR2023 100A to 3000A RMS 45Hz to 5kHz max conductor size 2.56in.
DRN-LEMFLEX3K 30A to 3000A RMS 8Hz to 7kHz max conductor size 6in.

The LEMFLEX-3K has been replaced by the  DRN-RR3035A-24/PS.
All future flex ct purchases will be for the  DRN-RR3035A-24/PS.

For flash card reader also see  DRN-FLASHREADER-USB.
LengthWidthHeightShip Wt 
12 " 2.5 " 8 " 45 lb  
    
N/A Currently not available for sale used
Need Configuration Assistance? Call our experienced Sales Staff.